当前位置: 代码迷 >> 综合 >> 西门子SCL编程:SCL编写的DCS电机块
  详细解决方案

西门子SCL编程:SCL编写的DCS电机块

热度:3   发布时间:2024-01-15 09:36:39.0

N年之前,用S7-300做一个小型DCS项目,选用wincc为人机界面。项目中电机、泵、风机类比较多,于是下功夫研究编写这个电机块。功能确实强大,在wincc中自动生成图标,拽出来直接用就可。

FUNCTION_BLOCK MOTOR1DIR_300
NAME:MOTOR1DIR
FAMILY:S7-300 BLOCK
AUTHOR:SDZYG2000
//VERSION:'1.01'
//FB620// Typical-Attribute
{S7_tasklist:='OB100';S7_m_c:='true';S7_blockview:='big'
}// Parameterattribute
// S7_visible       visible/unvisible   (default='true')
// S7_m_c           WinCC - Tag         (default='false')
// S7_dynamic       testmode            (default='false')
VAR_INPUTLOCK        {S7_dynamic:='true'} : BOOL := FALSE; // InterlockERR_EXTERN  {S7_dynamic:='true'} : BOOL := FALSE; // External ErrorLIOP_SEL    {S7_dynamic:='true'} : BOOL := FALSE; // 0=Operator 1=LinkingL_AUT       {S7_dynamic:='true'} : BOOL := FALSE; // 0=Manual 1=AutomaticL_REMOTE    {S7_dynamic:='true'} : BOOL := FALSE; // 0=Lokal 1=RemoteL_SIM       {S7_dynamic:='true'} : BOOL := FALSE; // 0=Normal 1=SimulationL_RESET     {S7_dynamic:='true'} : BOOL := FALSE; // 1=Reset Error PeripherieAUT_ON      {S7_dynamic:='true'} : BOOL := FALSE; // 1=CMD ON AutomaticMAN_ON      {S7_dynamic:='true'} : BOOL := FALSE; // 1=CMD ON ManualSIM_ON      {S7_dynamic:='true'} : BOOL := FALSE; // 1=CMD ON SimulationFB_ON       {S7_dynamic:='true'} : BOOL := FALSE; // Feedback MotorL_MON       {S7_dynamic:='true'} : BOOL := TRUE;  // 1=Monitoring ONMON_T       {S7_dynamic:='true'; S7_m_c := 'true'} : REAL := 10.0; // Monitoring TimeMPS         {S7_dynamic:='true'} : BOOL := FALSE; // 1=Motor Protecting Switch ONL_FLOW_MON  {S7_dynamic:='true'} : BOOL := FALSE; // 1=Monitoring FlowFLOW        {S7_dynamic:='true'} : REAL := 0.0;   // Current FlowFLOW_LL     {S7_dynamic:='true'} : REAL := 5.0;   // Low Level FlowFLOW_MT     {S7_dynamic:='true'; S7_m_c := 'true'} : REAL := 10.0;   // Monitoring Time FlowSAMPLE_T    {S7_sampletime:='true'} : REAL := 0.0; // Sample Time
END_VARVAR_IN_OUTOP_dwCmd    {S7_dynamic := 'true'; S7_m_c := 'true'} : DWORD :=0;   // control word wincc
END_VARVAR_OUTPUTQdwState    {S7_dynamic:='true'; S7_m_c:='true'}: DWORD:=0;     // status winccQabyState AT QdwState : ARRAY [0..3] OF BYTE;                   // look at state byte-wiseQwState     {S7_dynamic:='true'}: WORD:= 0; //0=off, 1=starting, 2=on, 3=stoppingQSTOPPING   {S7_dynamic:='true'} : BOOL := FALSE;     // 1=StoppingQSTOP       {S7_dynamic:='true'} : BOOL := FALSE;     // 1=StopQSTARTING   {S7_dynamic:='true'} : BOOL := FALSE;     // 1=StartingQRUN        {S7_dynamic:='true'} : BOOL := FALSE;     // 1=RunQCMD_ON     {S7_dynamic:='true'} : BOOL := FALSE;     // 0=Stop 1=StartQMON        {S7_dynamic:='true'} : BOOL := FALSE;     // 1=Monitoring FeedbackQMON_ERR    {S7_dynamic:='true'} : BOOL := FALSE;     // 1=Monitoring ErrorQMON_T      {S7_dynamic:='true'; S7_m_c := 'true'} : REAL := 0.0; // Current Monitoring Time FeedbackQFLOW_MON   {S7_dynamic:='true'} : BOOL := FALSE;     // 1=Monitoring FlowQFLOW_MT    {S7_dynamic:='true'; S7_m_c := 'true'} : REAL := 0.0; // Current Monitoring Time FlowQFLOW_ERR   {S7_dynamic:='true'} : BOOL := FALSE;     // 1=Error FlowQMPS        {S7_dynamic:='true'} : BOOL := FALSE;     // 1=Motor Protecting SwitchQERR        {S7_dynamic:='true'} : BOOL := FALSE;     // 1=ERRORQMAN_AUT   {S7_dynamic:='true'} : BOOL := FALSE;     // 0=Hand 1=AutomaticQREMOTE    {S7_dynamic:='true'} : BOOL := FALSE;     // 0=Local 1=RemoteQSIM       {S7_dynamic:='true'} : BOOL := FALSE;     // Simulaition is activeQLOCK      {S7_dynamic:='true'} : BOOL := FALSE;     // Interlock is activeQERR_EXT   {S7_dynamic:='true'} : BOOL := FALSE;     // External ERROR//AlarmQwAlarm    {S7_dynamic:='true'; S7_m_c := 'true'} : WORD := 16#0;   // Bit Alarm ProcedureQabyAlarm AT QwAlarm : ARRAY [0..1] OF BYTE;         // look at QwAlarm byte-wise
END_VARVAROPdwCmdHMI : DWORD := 16#0;                       // Operator Commands in HMI formatOPabyCmdHMI AT OPdwCmdHMI : ARRAY [0..3] OF BYTE; // look at HMI command byte-wiseOPdwCmdPLC : DWORD := 16#0;                       // Operator Commands in PLC formatOPabyCmdPLC AT OPdwCmdPLC : ARRAY [0..3] OF BYTE; // look at plc command byte-wiseOPabCmdPLC AT OPdwCmdPLC : ARRAY [0..31] OF BOOL; // look at plc command bit-wiseQdwStatePLC : DWORD := 16#0;                        // State word in PLC formatQabyStatePLC AT QdwStatePLC : ARRAY [0..3] OF BYTE; // look at state byte-wiseQabStatePLC AT QdwStatePLC : ARRAY [0..31] OF BOOL; // look at state bit-wiseQwAlarmPLC : WORD := 16#0;                          // Alarm Tag PLC FormatQabyAlarmPLC AT QwAlarmPLC : ARRAY [0..1] OF BYTE;  // look at Alarm byte-wiseQabAlarmPLC AT QwAlarmPLC : ARRAY [0..15] OF BOOL;  // look at Alarm bit-wise// TAGS for SimulationFB_SIM   : BOOL := FALSE;SIM_T    : REAL := 5.0;QCMD_SIM : BOOL := FALSE;// TAGS for OperationOP_RESET : BOOL := FALSE;// TAGS for Edge detectL_RESET_OLD : BOOL := FALSE;AUT_ON_OLD : BOOL := FALSE;MAN_ON_OLD : BOOL := FALSE;QSTARTING_OLD : BOOL := FALSE;QSTOPPING_OLD : BOOL := FALSE;END_VARVAR_TEMP
TOP_SI: STRUCTEV_CLASS  : BYTE;EV_NUM    : BYTE;PRIORITY  : BYTE;NUM       : BYTE;TYP2_3    : BYTE;TYP1      : BYTE;ZI1       : WORD;ZI2_3     : DWORD;
END_STRUCT;START_UP_SI: STRUCTEV_CLASS  : BYTE;EV_NUM    : BYTE;PRIORITY  : BYTE;NUM       : BYTE;TYP2_3    : BYTE;TYP1      : BYTE;ZI1       : WORD;ZI2_3     : DWORD;
END_STRUCT;
iRet     : INT;END_VARBEGIN// START UP =====================================================================iRet := SFC6 (TOP_SI:= TOP_SI, START_UP_SI:= START_UP_SI);IF (TOP_SI.NUM = 100) THENQCMD_ON   := FALSE;QSTOP     := TRUE;QSTARTING := FALSE;QRUN      := FALSE;QSTOPPING := FALSE;QwState := 0;iRet := 0;END_IF;
// END STARTUP ==================================================================// Change lowbyte to highbyte for HMI command word =====================OPdwCmdHMI := OP_dwCmd;OPabyCmdPLC[0] := OPabyCmdHMI[3];OPabyCmdPLC[1] := OPabyCmdHMI[2];OPabyCmdPLC[2] := OPabyCmdHMI[1];OPabyCmdPLC[3] := OPabyCmdHMI[0]; // ******************************************************************************
// Begin: Operation functions ***************************************************// MANUAL / AUTOMATIC Operation =======================================IF (LIOP_SEL AND NOT L_AUT) OR (OPabCmdPLC[16] AND NOT LIOP_SEL) THEN QMAN_AUT := FALSE;ELSIF (LIOP_SEL AND L_AUT) OR (OPabCmdPLC[17] AND NOT LIOP_SEL) THEN QMAN_AUT := TRUE;END_IF;// LOCAL / REMOTE Operation =========================================IF (LIOP_SEL AND NOT L_REMOTE) OR (OPabCmdPLC[18] AND NOT LIOP_SEL) THENQREMOTE := FALSE;ELSIF (LIOP_SEL AND L_REMOTE) OR (OPabCmdPLC[19] AND NOT LIOP_SEL) THENQREMOTE := TRUE;END_IF;// SIMULATION ON / OFF ==============================================IF (LIOP_SEL AND NOT L_SIM) OR (OPabCmdPLC[20] AND NOT LIOP_SEL) THENQSIM := FALSE;ELSIF (LIOP_SEL AND L_SIM) OR (OPabCmdPLC[21] AND NOT LIOP_SEL) THENQSIM := TRUE;QCMD_ON := FALSE;END_IF;// RESET Operation ==================================================IF (LIOP_SEL AND L_RESET AND NOT L_RESET_OLD) OR (OPabCmdPLC[24] AND NOT LIOP_SEL) THENOP_RESET := TRUE;ELSEOP_RESET := FALSE;END_IF;// MONITORING FEEDBACK ON / OFF =====================================IF (LIOP_SEL AND L_MON) OR (OPabCmdPLC[8] AND NOT LIOP_SEL) THENQMON := TRUE;ELSIF (LIOP_SEL AND NOT L_MON) OR (OPabCmdPLC[9] AND NOT LIOP_SEL) THENQMON := FALSE;END_IF;// MONITORING FLOW ON / OFF =========================================IF (LIOP_SEL AND L_FLOW_MON) OR (OPabCmdPLC[10] AND NOT LIOP_SEL) THENQFLOW_MON := TRUE;ELSIF (LIOP_SEL AND NOT L_FLOW_MON) OR (OPabCmdPLC[11] AND NOT LIOP_SEL) THENQFLOW_MON := FALSE;END_IF;// START / STOP Motor (AUTOMATIC)====================================IF (QMAN_AUT AND AUT_ON AND NOT AUT_ON_OLD AND NOT QSIM) THENQCMD_ON := TRUE;ELSIF (QMAN_AUT AND NOT AUT_ON AND NOT QSIM) THENQCMD_ON := FALSE;END_IF;// START / STOP Motor (MANUAL)=======================================IF (NOT QMAN_AUT AND NOT QREMOTE AND MAN_ON AND NOT MAN_ON_OLD AND NOT QSIM) OR (OPabCmdPLC[1] AND NOT QMAN_AUT AND QREMOTE AND NOT QSIM)  THENQCMD_ON := TRUE;ELSIF (NOT QMAN_AUT AND NOT QREMOTE AND NOT MAN_ON AND NOT QSIM) OR (OPabCmdPLC[0] AND NOT QMAN_AUT AND QREMOTE AND NOT QSIM) THENQCMD_ON := FALSE;END_IF;// START / STOP Motor (SIMULATION)===================================IF (QSIM AND NOT QREMOTE AND SIM_ON) OR (OPabCmdPLC[1] AND QREMOTE AND QSIM) THENQCMD_SIM := TRUE;ELSIF (QSIM AND NOT QREMOTE AND NOT SIM_ON) OR (OPabCmdPLC[0] AND QREMOTE AND QSIM) THENQCMD_SIM := FALSE;END_IF;// END: Operation functions *****************************************************
// ******************************************************************************    //=================================
//            QwState
//0 = Stop
//1 = Starting
//2 = Run
//3 = Stopping
//=================================//--------------------------
//QwState = 0; Stop
//--------------------------IF NOT QSIM THEN    // *** Process Mode ***IF (NOT QCMD_ON AND QwState=3 AND NOT QMON_ERR AND NOT FB_ON) OR(NOT QCMD_ON AND QwState=3 AND NOT QMON)THENQSTOP     := TRUE;QSTARTING := FALSE;QRUN      := FALSE;QSTOPPING := FALSE;QwState := 0;END_IF;ELSE                // *** Simulation Mode ***IF (NOT QCMD_SIM AND QwState=3 AND NOT FB_SIM) OR(NOT QCMD_SIM AND QwState=3 AND NOT QMON)THENQSTOP     := TRUE;QSTARTING := FALSE;QRUN      := FALSE;QSTOPPING := FALSE;QwState := 0;END_IF;END_IF;//--------------------------
//QwState = 1; Starting
//--------------------------IF NOT QSIM THEN    // *** Process Mode ***IF (QCMD_ON AND QwState = 0) THEN QSTOP     := FALSE;QSTARTING := TRUE;QRUN      := FALSE;QSTOPPING := FALSE;QwState := 1;END_IF;ELSE                // *** Simulation Mode ***IF (QCMD_SIM AND QwState = 0) THEN QSTOP     := FALSE;QSTARTING := TRUE;QRUN      := FALSE;QSTOPPING := FALSE;QwState := 1;END_IF;END_IF;//--------------------------
//QwState = 2; RUN
//--------------------------IF NOT QSIM THEN        // *** Process Mode ***IF (QCMD_ON AND QwState=1 AND NOT QMON_ERR AND FB_ON) OR(QCMD_ON AND QwState=1 AND NOT QMON)THENQSTOP     := FALSE;QSTARTING := FALSE;QRUN      := TRUE;QSTOPPING := FALSE;QwState := 2;END_IF;ELSE                    // *** Simulation Mode ***IF  (QCMD_SIM AND QwState=1 AND FB_SIM) OR(QCMD_SIM AND QwState=1 AND NOT QMON)THENQSTOP     := FALSE;QSTARTING := FALSE;QRUN      := TRUE;QSTOPPING := FALSE;QwState := 2;END_IF;END_IF;//--------------------------
//QwState = 3; Stopping
//--------------------------IF NOT QSIM THEN        // *** Process Mode ***IF (NOT QCMD_ON AND (QwState = 1 OR QwState = 2)) THENQSTOP     := FALSE;QSTARTING := FALSE;QRUN      := FALSE;QSTOPPING := TRUE;QwState := 3;END_IF;ELSE                    // *** Simulation Mode ***IF (NOT QCMD_SIM AND (QwState = 1 OR QwState = 2)) THENQSTOP     := FALSE;QSTARTING := FALSE;QRUN      := FALSE;QSTOPPING := TRUE;QwState := 3;END_IF;END_IF;// Feedback Monitoring =================================================IF QMON THENIF (QSTARTING AND NOT QSTARTING_OLD) OR (QSTOPPING AND NOT QSTOPPING_OLD) THENQMON_T := 0.0;END_IF;IF NOT QSIM THEN    // *** Process Mode ****IF (QSTARTING OR QSTOPPING) THENQMON_T := QMON_T + SAMPLE_T;IF (QMON_T >= MON_T) THENQMON_ERR := TRUE;END_IF;ELSEQMON_T := 0.0;END_IF;IF (QRUN AND NOT FB_ON) OR (QSTOP AND FB_ON) THENQMON_ERR := TRUE;END_IF;  ELSE               // *** Simulation Mode ***IF (QSTARTING) THENQMON_T := QMON_T + SAMPLE_T;IF (QMON_T >= SIM_T) THENFB_SIM := TRUE;END_IF;ELSIF (QSTOPPING) THENQMON_T := QMON_T + SAMPLE_T;IF (QMON_T >= SIM_T) THENFB_SIM := FALSE;END_IF;ELSEQMON_T := 0.0;END_IF;END_IF;END_IF;
// END Monitoring ======================================================// Check Errors ========================================================QERR_EXT := ERR_EXTERN;IF LOCK AND (QSTARTING OR QRUN) THENQLOCK := TRUE;END_IF;IF MPS THENQMPS := TRUE;END_IF;QERR := QERR_EXT OR QMON_ERR OR QFLOW_ERR OR QLOCK OR QMPS;// RESET Errors ========================================================IF OP_RESET THENQMON_ERR  := FALSE;QFLOW_ERR := FALSE;QMPS      := FALSE;QLOCK     := FALSE;END_IF;// If Error then Stop ==================================================        IF QERR THENQSTOP     := TRUE;QSTARTING := FALSE;QRUN      := FALSE;QSTOPPING := FALSE;QCMD_ON   := FALSE;QCMD_SIM  := FALSE;QwState   := 0;QMON_T    := 0.0;END_IF;// Set State for HMI ===================================================QabStatePLC[0]  := QSTOP;       // 1=StopQabStatePLC[1]  := QSTARTING;   // 1=StartingQabStatePLC[2]  := QRUN;        // 1=RunQabStatePLC[3]  := QSTOPPING;   // 1=StoppingQabStatePLC[4]  := 0;QabStatePLC[5]  := 0;QabStatePLC[6]  := 0;QabStatePLC[7]  := 0;   QabStatePLC[8]  := QMON;        // 1=Feedback Monitoring ONQabStatePLC[9]  := QMON_ERR;    // 1=Error Feedback MonitoringQabStatePLC[10] := QFLOW_MON;   // 1=Flow Monitoring ONQabStatePLC[11] := QFLOW_ERR;   // 1=Error Flow MonitoringQabStatePLC[12] := QMPS;        // 1=Motor Protecting SwitchQabStatePLC[13] := 0;QabStatePLC[14] := 0;QabStatePLC[15] := 0;QabStatePLC[16] := QMAN_AUT;    // 0=Manual 1=AutomaticQabStatePLC[17] := QREMOTE;     // 0=Local 1=RemoteQabStatePLC[18] := QSIM;        // 0=Process 1=Simulation QabStatePLC[19] := 0;QabStatePLC[20] := 0;QabStatePLC[21] := 0;QabStatePLC[22] := 0;QabStatePLC[23] := 0;QabStatePLC[24] := QERR;        // 1=ErrorQabStatePLC[25] := QERR_EXT;    // 1=External ErrorQabStatePLC[26] := QLOCK;       // 1=Motor Locked;QabStatePLC[27] := LOCK;        // 1=INTERLOCKQabStatePLC[28] := 0;  QabStatePLC[29] := 0;  QabStatePLC[30] := 0;QabStatePLC[31] := 0;QabyState[0] :=QabyStatePLC[3];QabyState[1] :=QabyStatePLC[2];QabyState[2] :=QabyStatePLC[1];QabyState[3] :=QabyStatePLC[0];// Bit alarm procedure ================================================QabAlarmPLC[0] :=QMON_ERR;      // Feedback ErrorQabAlarmPLC[1] :=QFLOW_ERR;     // Flowing ErrorQabAlarmPLC[2] :=QMPS;          // Motor ProtectQabAlarmPLC[3] :=0;         QabAlarmPLC[4] :=QLOCK;         // Interlock ErrorQabAlarmPLC[5] :=0;QabAlarmPLC[6] :=QERR_EXT;      // External ErrorQabAlarmPLC[7] :=QERR;          // General ErrorQabAlarmPLC[8] :=QSTOP;         // StopQabAlarmPLC[9] :=QSTARTING;     // StartingQabAlarmPLC[10] :=QRUN;         // RunQabAlarmPLC[11] :=QSTOPPING;    // StoppingQabAlarmPLC[12] :=LOCK;         // InterlockQabAlarmPLC[13] :=QREMOTE;      // RemoteQabAlarmPLC[14] :=QMAN_AUT;     // AutomaticQabAlarmPLC[15] :=QSIM;         // SimulationQabyAlarm[0] := QabyAlarmPLC[1];QabyAlarm[1] := QabyAlarmPLC[0];// Set Tags for edge detect =====================================L_RESET_OLD := L_RESET;AUT_ON_OLD := AUT_ON;MAN_ON_OLD := MAN_ON;QSTARTING_OLD:= QSTARTING;QSTOPPING_OLD:= QSTOPPING;//reset commands ================================================OP_dwCmd := 16#0;
END_FUNCTION_BLOCK

 

  相关解决方案